My Rinnai 1004F giving me error code 99

My Rinnai 1004F direct-vent wall furnace is giving me error code 99. it won't light up.? Mfr Manual says of the error code 99: Flue Block Check around the flue terminal for blockage. I checked and there is no blockage. So when I turn it on, air intake goes on for few seconds then it stops with error code 99. Any idea what is wrong?

Posted by on

Ad

1 Answer

  • Level 3:

    An expert who has achieved level 3 by getting 1000 points

    All-Star:

    An expert that got 10 achievements.

    MVP:

    An expert that got 5 achievements.

    Vice President:

    An expert whose answer got voted for 100 times.

  • Master
  • 451 Answers

This fusible link may be open. Try jumpering the two leads and see if the unit operates. If it does replace the fusible link. Do not operate the unit without the fusible link for an extended period. It is a safety device and is there for a reason. Hope this helps.

Posted on Jan 04, 2014

Testimonial: "Thanks for the info. By the fusible link, did you mean the part F (Fuse) or the thermal fuse (TF) which consists of TF1, TF2 amd TF3?"

Ad

4 Suggested Answers

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
goodluck!

Posted on Jan 02, 2017

Ad
Therinnaiguy
  • 1420 Answers

SOURCE: Rinnai RHFE 1004F Error code 49

A 49 error code is caused by the pressure switch either not proving or a bad component. Check the hose attached from the plastic elbow located behind the heater going to a small square pressure switch found inside the heater. It may have come loose or a mouse may have taken a bite out of it. Also while you are behind the heater, pull off the hose that looks like a vacuum cleaner hose and run the heater with it unattached. If it runs, you have a blockage in the vent. If not, take a flashlight and go outside to the vent. Look down the center pipe for any obstructions. If it still does not work, you may need a new pressure switch.

While the front panel is off the heater, cycle the heater to attempt a start. You want to make sure the blower turns. If it does not, check the wire connections to it. You may be looking at a bad blower. If it is turning but still does not start, we are looking at a bad pressure switch.

Let me know what you find, I may have a switch or blower motor that you can purchase.

Posted on Nov 01, 2007

  • 1 Answer

SOURCE: Replacing a Rinnai 403 FT

gday nelson. if you check out the specs on the rinnai range you will find another one that will go straight in. if you buy new it will come with a new flue kit. as far as recomended installation heights most of them are quite flexible. i installed a second hand 403ft yesterday with the centre of the flue at 140mm from the floor. recomended in the instructions were 240mm. a mate gave me the heater and i just had to buy a flue kit as the old one was already too short. if you messure your flue from inside and send me the specs i can give you a more difinitive answer.

Posted on Jul 12, 2008

Therinnaiguy
  • 1420 Answers

SOURCE: need to move the unit by dismantling

Remove the two screws on the side trim. Remove the two top screws from the filter panel. Reach behind the heater and pull the sock down on the vent pipe. unclip the two clamps holding the vent pipe together. Remove the plastic elbow off of the vent termination. Slide the heater to the left to slide the vent pipe off of the vent termination. Remove the gas line after shutting the gas off.

Posted on Dec 30, 2008

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

What is error code 99 on my Rinnai energysaver wall heater


Check the flue for blockage of exaust air flow ,ice,snow,birdnest ect.

Feb 18, 2015 | Rinnai RHFE-1004FA 38,400 BTU Energy Saver...

1 Answer

Our red filter light is on and we have cleaned everything and now it makes 5 beeps every few minutes constantly


Check the air switch and tubing, if everything is clean, the switch is defective, the tubing is plugged or disconnected/broken.

Feb 10, 2015 | Rinnai Energy Saver Direct Vent Wall...

1 Answer

Need pilot light assembly for Rinnai gas heater model #REH-25-P


Unfortunately, Rinnai only sells repair parts through their authorized dealers. Contact the dealer you purchased it from. If you are not the original owner of the home/heater, you can go to Rinnai's website and search for a dealer near you. http://www.rinnai.us/direct-vent-wall-furnaces/

Feb 28, 2011 | Rinnai RHFE-1004FA 38,400 BTU Energy Saver...

1 Answer

Rinnai direct vent heater RHFE 556WTA goes off showing code 99 which means flue block we have checked flue terminal and still have same problem. I understand their is a recall on some please let us know...


Remove the top panel closest to the wall after you remove filter. Check all the connections for exhaust and air intake. You can remove the air intake pipe (looks like a smaller diameter vacuum cleaner hose but Gray in color) and run the unit with it off of the vent. If unit starts and stays on, the inducer blower is getting weak and will need to be replaced. There is also two small hoses (clear and blue) that may have come off the vent or even cracked or chewed by a mouse. Inspect them for cracks or damage. You may have to take off the right side panel closest to the wall to get to the hoses. Next, remove the many screws that hold the front panel on the heater. Take off the front cover and check to make sure all the hoses are connected and that the inducer fan runs. You can even take a shop vacuum and put it over the center hole on the vent to make sure something is not lodged inside where you can't see it.

Yes there is a recall for a gasket that deteriorates over time. It is located at the view port of the flame. Contact Rinnai at (US) 8006219419 for details.

Hope this helps.

Feb 24, 2011 | Rinnai RHFE-556WTA Direct Vent Heater NG...

1 Answer

Usually my rinnai 1004f is set at 64 and reads out about 66 or so. This morning I woke up and it read 48 and was freezing cold in my house. I tried cleaning out both filters and looking outside to make...


You can get any error code that may be stored by pressing on the Economy button and the UP and Down arrows all at the same time and hold for 5 or 6 seconds. This may get you a start on what may be the problem. Post them when you get them. If you do not get any error codes, remove the right side panel closest to the wall and look for a small black rubber bulb. That is the thermostat for the unit. If you hold it with your fingers, it should show a higher temp. I am afraid that you are going to need a technician who is familiar with Rinnai heaters if you can't get it going.

Jan 24, 2011 | Rinnai RHFE-1004FA 38,400 BTU Energy Saver...

1 Answer

I have a Rinnai 1004F, no manual. Vent Contol Button is in open position, its winter, should vent be closed at all? Economy button, whats it for?


Not sure about Vent Control however the Economy button is like a night time set back. Over a 2 hour period it will decrease the temperature up to 6 degrees from set point. In morning, just take off economy and unit will come up to temp. Go to www.rinnai.us for on-line manual.

Nov 28, 2010 | Rinnai RHFE-1004FA 38,400 BTU Energy Saver...

1 Answer

After being off all summer i click on but it wont fire up i checked for carbon the tank is full i have a rinnai 1004f


Do you get an error code? 11. 12 68, 72, etc. Does the combustion motor come on. You should be able to hear it. Is the exhaust and air pipe clear? Is the air hose hooked to the back of the stove?

Tom

Sep 17, 2010 | Rinnai RHFE-431FAIII 16,700 BTU Direct...

1 Answer

Code 99 flash after 5 min and then turn off


Flue block or venting disconnected. You could be getting cross contamination or the flue termination could be iced up. Check it out closely. There is also a recall from Rinnai for a retrofit kit. Contact your gas service provider with the serial number of the unit and they will tell you if yours is under the recall.

Feb 16, 2010 | Rinnai RHFE-556WTA Direct Vent Heater NG...

1 Answer

Can you vent the Rinnai 551F vertically through ceiling?


This unit can be vented through the roof but requires a specialized flue system-do not use an existing flue connection. Call a contractor - have them check and see if the unit can be modified to a vertical flue- it will require the existing piping to be replaced--Not a job for a do-it yourselfer

Nov 01, 2009 | Rinnai RHFE-1004FA 38,400 BTU Energy Saver...

Not finding what you are looking for?
Rinnai RHFE-1004FA 38,400 BTU Energy Saver Ductless Heater - LP Gas Logo

601 people viewed this question

Ask a Question

Usually answered in minutes!

Top Rinnai Heating & Cooling Experts

paulcarew

Level 3 Expert

2516 Answers

Dan Webster
Dan Webster

Level 3 Expert

8220 Answers

Tim Whalen

Level 3 Expert

3074 Answers

Are you a Rinnai Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...