Question about Heating & Cooling

1 Answer

Sanyo 12KS71 Split Air Conditioner

Installed in 5/07, ran fine for 3 months, then it would not start - no lights, nothing. Reset breaker and it ran fine, cold air. Then it quit. Now sometimes it runs, sometimes it is dead. Replaced batteries in control. No luck. Once when it would not start, I checked voltage = 115.9, also has voltage on the protection line. How do you determine if it is the remote or one of the two circuit boards? Any suggestions would be helpful.

Posted by on

  • smokinhotime Nov 11, 2007

    Unit ran well for about 2 months then it just stopped. I checked the voltage going into the inside unit whick was ok. I changed batteries in the remote, still no go. About 1 week after giving up on starting the unit, it starts up. I did nothing during the 1 week. It now runs for 2 or 3 days then just stops (with me doing nothing). You go figure. The dealer is sending me a new circuit board.

  • Anonymous Jan 28, 2009

    Hi, i dont understand the remote control. i changed the battery, but cant seem to get the right settings for the air conditioner to cool right. its a SANYO SAP. Please Help!

×

Ad

1 Answer

  • Level 2:

    An expert who has achieved level 2 by getting 100 points

    All-Star:

    An expert that got 10 achievements.

    MVP:

    An expert that got 5 achievements.

    Vice President:

    An expert whose answer got voted for 100 times.

  • Expert
  • 236 Answers

Check your remote control the timer may be activated. Or try to push the reset button on your remote control to set it to default setting or just pull out the battery then insert it again then try. If problem persist then qualified technician is needed.

Posted on Jan 15, 2008

Ad

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi there,
Save hours of searching online or wasting money on unnecessary repairs by talking to a 6YA Expert who can help you resolve this issue over the phone in a minute or two.

Best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.

Here's a link to this great service

Good luck!

Posted on Jan 02, 2017

Ad

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

Have a Sanyo KS2472 split inverter unit. On turning it on, operation light blinks and does not cool. Also compressor does not seem like it turns on outside. Please help.


The blinking is an indicator that it needs service. Call a technician! Ask if they are experienced in mini split systems. You can check the air filters. Check the outdoor coil to see if its clean or covered up with dirt. And at the breaker or disconnect, turn off power, wait 5 mins, and turn it back on. Then give it 3-5 mins to see if it will reset itself. If this don't work, call a tech/service provider! These units are troublesome to troubleshoot.

Jun 06, 2015 | Sanyo Heating & Cooling

1 Answer

I have a sanyo split system and one of the inside units creates ice around the coils. the filters are clean and there's nothing blocking the air around it. What can it be?


There are reasons for.
1. Dusty indoor coil and blower wheel - Clean it.
2. Less speed of blower motor- Replace capacitor/motor
3. Short of gas- Find leak and rectify.

Thanks.

Jun 29, 2011 | Sanyo Split System Air Conditioner

1 Answer

AMCOR 24,000 BTU split system. Worked fine two years, then today it had no power. Checked circuit breaker, it had popped. Reset CB and went to inside unit - would not turn on or off with remote or hard...


I had this same problem. I disconnected the thermostat wire out side at the condenser and reconnected it and it started working. A couple days later it blew the breaker again this time I found the bus where the L1, L2. GR wire connect at the condenser had melted. I wire nutted all 3 wires instead of the using the bus everything is working right again. Hope this helps.
Tim

Aug 09, 2010 | AmcorAire UCHW-H24AF2 Split System Air...

2 Answers

Remote does not turn on or off the Split System Air Conditioner


take your cellphone and turn on the camera,then put the remote in front of the cell and push any button.if you see the light of the remote to the cell then the remote is ok and the problem is to the eye of the plate.its a small plate in front of the split

May 08, 2009 | Sanyo 18KS52 Air Conditioner

1 Answer

Condensation from the coils


check drain hose maybe is obstruct or have bad plunk.

Feb 12, 2009 | Sanyo 09KS51 Mini Split Air Conditioner

1 Answer

Heat controller mini-split air conditioner


Check each screw on your compressor to ground (compressor case). Should be very high resistance Then check the resistance across your teminals on the compressor to be sure it is not shorted. Then check the wiring to your capacitor (The big one). I ran across this just last week. The mechanic didnt have the capicator wired correctly. If it is brand new it will have a wiring schematic somewhere on it.
Dont leave the compressor on very long, but turn it on long enough to get a voltage reading across the terminals. I assume it should be 240 volts. If you have check all of this, they make a jump start gadget to start a stuck compressor. They sell it just about everywhere. Let me know how this comes out..

Sep 30, 2008 | Sanyo 24KS62R Cool Mini Split Air...

1 Answer

Kenmore Model #731893 Room Air Conditioner


Does you air conditioner have a GFCI on the end of the plug if it does there is a reset there.. let me know if it doesn't and you want to go deeper?

Aug 07, 2007 | Kenmore 73189 Air Conditioner

1 Answer

LG split system air conditionsr


3 flases indicates a communication error. Have a technician check wiring and connections.

Jun 05, 2007 | LG LSC121PMA Split System Air Conditioner

Not finding what you are looking for?
Heating & Cooling Logo

Related Topics:

692 people viewed this question

Ask a Question

Usually answered in minutes!

Top Heating & Cooling Experts

Paul Carew

Level 3 Expert

3328 Answers

Tim Whalen

Level 3 Expert

3074 Answers

Marvin
Marvin

Level 3 Expert

81400 Answers

Are you a Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...