Are you saying that on PQ log software line 3 is red? Is this the third phase of the measurement?
yes the third phase
that is the color code for that phase. It does not mean anything is wrong.
yes but its reading 172V and the volt meter is reading 204V
Calibration of both items not being questioned, do you have scaling set and what is the interval?
the fluke is 172v showing red as a under-voltage but a greenlee clamp on isshowing the blue at 204V which is correct
Measure something else with those probes and see if the say the same thing. That would rule out any parasitic interference that one of the probes might have and issue with or any calibration issues.
×