Question about Desa International Blower Glow Warm Wall Heater

1 Answer

The first plaque does not turn blue in all places some have black

Glo Warm Plaque Not Working

Do i need to clean or replace-can not use it on low.

Posted by on

1 Answer

  • Level 1:

    An expert who has achieved level 1.

    Corporal:

    An expert that has over 10 points.

    Problem Solver:

    An expert who has answered 5 questions.

  • Contributor
  • 16 Answers

Over time the heater will accumulate "lint" from its surroundings,
a service person should be able to dismantle and clean all areas of the heater and plaques removing the lint and this 95% of the time will fix the problem.
Note: this type of service should be performed at least once every 2 years or sooner depending of the amount of usage.

Posted on Feb 16, 2009

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

I have a GloWarm propane/lp gas space heater. Can I use bottled propane tanks?


no you can't, and aren't you worried about carbon monoxide poisoning? Where does the burnt air go?

GloWarm Heaters - ventfree infrared heaters
GloWarm Infrared heaters are residential gas space heaters that are ventfree,
so no venting is required

GloWarm Plaque Infrared heaters direct heat from radiant plaques that
"warm like the sun."

Infrared heaters heat objects in the room before the air,
making them ideal for un-insulated rooms in your home.

All propane heaters require a 100 lb. tank or larger!

GloWarm Heaters ventfree infrared heaters

Oct 27, 2015 | Heaters

1 Answer

MY PANEL HEATER IS CRACKED. IT STILL WORKS. CAN I FIX IT.


If you're referring to one of the ceramic plaques in an infrared heater? Yes, the plaque(s) can be replaced. However, the heater should not be used until the plaque(s) is replaced.

Without knowing what Brand heater you have and the correct Model Number, I have no way to tell you were to find the plaque you need.

Jul 08, 2011 | General Heaters

1 Answer

My glo warm plaq doesnt glow red but has flame.thanks


The plaque may be out of place or may need replacing, depending on the age of the heater.
Also, although you have flame, make sure you have flame at that plaque that's equal to the other plaques. If you don't the burner may simply need cleaning.

Feb 13, 2011 | Rinnai Desa Vent-Free Infrared Gas Heater:...

1 Answer

The center ceramic segment does not glow red like the outside ones, it stays more blue, is there a flame adjustment?


No, no flame adjustment, but that section of the burner, behind the plaque may be clogged. If you don't service your heater at least annually or have it serviced annually, more than likely that's the problem. Also, check the condition of the plaque in question. Depending on the age of the heater, it may simply be cracked or worn out.

If you discover it needs replacement you can order one from FMI (the company that bought part of DESA International after the bankrupted) by calling 868-328-6951, then press 2.. You will need to have the Model # & Serial # of your heater when you call.

Feb 09, 2011 | Desa International Blower Glow Warm Wall...

1 Answer

I have a glo warm gwrn30a a flame shoots over the top of the center plaque about a inch or sol


Check to see that the center (plaque) is seated in its holder securely. Also make sure these (plaques) are clean and there are no obstructions so gas can flow freely thru them. Easy hint for cleaning them is a compressor and blow gun, using pressurized air and blowing them out clean. Try this and it just could solve your problem.

Dec 22, 2010 | Desa International Blower Glow Warm Wall...

1 Answer

Wont stay lit


If dust gets into the pilot safety device called an ODS (oxygen depletion sensor) then the safety thinks the air is low and kicks the pilot off. To remedy it I flush the pilot with a little rust buster. This cleans the dust out without disturbing the air flap. I have repair photos and a neat demo video that shows how it works HERE

Feb 21, 2010 | Dyna-Glo D-E36 Infra-Red Wall Mounted...

1 Answer

Pro com plaques breaking down


You may want to try Master Parts, they may have the plaques. The problem with replacing the plaques is that they can be expenise to replace. Sometimes its the same price just to replace the total unit.

Nov 26, 2008 | Procom 10K BTU, Vent Free, 2 Plaque...

1 Answer

Vent free infared heater


What you are experiencing is common if the plaques are either out of alignment or the burner is dirty. I know you said you cleaned it with low pressure air, but you need at least 120 PS. of air to clean the burner and plaques as per the owners manual.

Nov 12, 2007 | Rinnai Desa Vent-Free Infrared Gas Heater:...

Not finding what you are looking for?
Desa International Blower Glow Warm Wall Heater Logo

Related Topics:

229 people viewed this question

Ask a Question

Usually answered in minutes!

Top Desa International Heaters Experts

paulcarew

Level 3 Expert

1914 Answers

Dan Webster
Dan Webster

Level 3 Expert

8147 Answers

Gil Shultz

Level 3 Expert

3250 Answers

Are you a Desa International Heater Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...