Goodman Dependable 92 blowign cold air only - no heat

Goodman Dependable 92 blowing cold air only

Posted by on

  • carl carpenter
    carl carpenter May 11, 2010

    is it gas or electric heat or is it a heat pump?

  • Dan Webster
    Dan Webster May 11, 2010

    Gas,electric ,or heatpump?

×

1 Answer

  • Level 1:

    An expert who has achieved level 1.

    Corporal:

    An expert that hasĀ over 10 points.

    Problem Solver:

    An expert who has answered 5 questions.

  • Contributor
  • 13 Answers

Blowing cold air on this furnace usualy caused by high limit trip, or flame roll out. the first one, (high limit) is from insf. air flow. (blocked filter,bad zone damper?
The second,(flame roll out) caused by bad heat exchanger,blocked vent.ect.

Posted on Jan 11, 2009

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

I have a Goodman CPE30-1AB (Outside heat exchanger), with a Goodman (air blower) as well. Air blows inside, but not cold. Outside unit is not turning on at all. Can you please assist?


check your breaker or fuses at outside unit. verify you have 24 volts feeding outside unit replace outside unit contactor if you have the 24 volts and not starting.

Aug 08, 2015 | Goodman Air Conditioners

1 Answer

Thermostat wiring diaghram for pc/ph15 m series heat pump


Contact Goodman directly to request the wiring diagram.

Oct 09, 2014 | Goodman Manufacturing Goodman...

1 Answer

Central heat not blow hot air


you posted in november if it was very cold auxillary heat issue.

Nov 11, 2013 | Goodman Air Conditioners

1 Answer

Goodman model aruf486016AA is not blowing hot air


Need more info. Does blower come on when calling for heat?

Nov 11, 2013 | Goodman Manufacturing Goodman ARUF486016...

1 Answer

Unit is blowing cold air but temp. stays around 75; heat is not being displaced.


Hi,
Your heat gain is great then the capacity of the unit you are using to cool with...

Here is a tip about trouble shooting your air conditioner...

Air Conditioner Trouble -Review the Possibilities
http://www.fixya.com/support/r3571569-air_conditioner_trouble_review_the_possi

heatman101

Jul 18, 2010 | Goodman Air Conditioners

1 Answer

I have a 3 ton goodman heat pump warm air is delivered from all the vents except for two which blows cool to cold air . help me , freezing im both bedrooms


if these are the longest runs from the air handler this can sometimes happen ,about the easest solution is to install a in duct heater into the duct feeding the rooms this is basically a set of electric coils installed in duct to re-heat the air going to the bed room

Jan 08, 2010 | Goodman CLQ36AR49 Air Conditioner

1 Answer

Its 28 degrees out side and my goodman 3.5 ton heat pump package unit is blowing cold air out of all my regesters


Sounds like the heat pump is not running. Check outside to see if the fan is spinning.

Try moving the thermostat to emergency heat and see if that gives you any heat. If it does, then you have heat until you can get a service technician to locate the problem with the heat pump. It could be a wide range if issues from bad thermostat to bad wiring to bad capacitor.

Jan 07, 2010 | Goodman Air Conditioners

1 Answer

I have a goodman ac/heat pump....worked fine last season...now only blows cold air, even in heat setting....help! thanx


Heat Pumps are not famous for being fast heaters. Give it some time to act. Is yours extracting heat from the air or from a water source. If from the outside air, consideration must be given to the temp of the outside air. It takes longer to warm as the temp outside drops.

Yours could be a different problem of course, but let it have a chance to work before you call the repairman.

Dec 12, 2009 | Goodman CLQ36AR49 Air Conditioner

2 Answers

AC unit outside blowing out cold air, vents


Sounds like compressor not running. may be a bad capacitor, could also be low on freon.

Aug 30, 2009 | Goodman CLJ30AR32 Air Conditioner

1 Answer

WHEN THE HEATER COMES ON THE FAN STARTS INSTANTLY AND BLOWS COLD


Do you have a heat pump? If so this is normal. You are probably used to a gas furnace. There are heat pumps that do have a delay though. Look on the circuit board in the air handler. There may be a set of pins that say 0-30-60-90 yours may be at 0. Also some digital T-stats offer that function for delay off to get the extra heat or cold from the system. Find out what the model number of the air handler and call the Goodman supplier in your area to see if you have these options.
If you have a gas furnace and it's not delaying the blower there is definately something wrong.

Mar 17, 2009 | Goodman Air Conditioners

Not finding what you are looking for?
Air Conditioners Logo

Related Topics:

429 people viewed this question

Ask a Question

Usually answered in minutes!

Top Air Conditioners Experts

Dan Webster
Dan Webster

Level 3 Expert

8147 Answers

Bill Long

Level 3 Expert

577 Answers

Tim Whalen

Level 3 Expert

3056 Answers

Are you an Air Conditioner Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...