Question about Kitchen Appliances - Others

1 Answer

Blower will not come on

My heater coils heat up but the fan will not come on it is an intertherm e2eb-017ha electric furnace

Posted by on

  • Anonymous Mar 10, 2009

    HAVE TURNED THE FAN ON MANUAL AT THE THERMOSTAT AND WORKS FINE WHICH SEQUENCER CONTROLS THE FAN

×

1 Answer

  • Level 2:

    An expert who has achieved level 2 by getting 100 points

    MVP:

    An expert that gotĀ 5 achievements.

    Governor:

    An expert whose answer gotĀ voted for 20 times.

    Hot-Shot:

    An expert who has answered 20 questions.

  • Expert
  • 82 Answers

Could be the fan relay is bad. or the run capacitor. if these check good. you may have a bad heat sequencer. hard to tell, if you thave a/c you can turn thermostat fan swith to on and if blower comes on then relay and capacitor should be ok. some units have two or three heat sequencers 1 controls fan and the others control heat strips hopefully this helps good luck

Posted on Jan 04, 2009

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
goodluck!

Posted on Jan 02, 2017

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

I have a intertherm model e2eb-017ha the blower wont shut off i have to turn the braker off


One The blower relay is stuck in the on position. Two at the thermostat, fan switch should be set to auto. Set it on the blower wont quit.

Jan 29, 2014 | Intertherm Heating & Cooling

1 Answer

I have a E2EB-017HA air handler and I want to change it to a variable speed motor. Is this possible


Some companies do sell a variable speed kit. It includes the motor and controls. Get your model and serial number of your unit and contact your local Payne dealer. The can locate the proper kit if available for you.

Feb 03, 2013 | Intertherm E3EB-017H Furnace 17Kw 2

1 Answer

E2EB-017HA HOW TO SLOW SPEED DOWN ON BLOWER


Go to the blower motor find 3 wires.Black is high,blue is med, red is slow. Find what wire is on blower relay. then adjust to what you what. hope this helps.

Aug 21, 2011 | Intertherm P3RA-048K Air Conditioner

1 Answer

I have a Intertherm Heat Pump system in my Manufactured Home, Model # E2EB-015HB; Serial # E2E0121006692. Condensation is forming on the Coils and the water fills up the area under the coils, drips down...


There is a drip pan bit the middle is open to allow air flow through the coil and into your ducting. If the drain for the drip pan is clogged it will fill up and overflow onto your furnace and then to the floor.If that is what is happening then clean out the drain tube running down the front of the furnace and it should empty the drip pan and solve your problem.

You also need to have your furnace checked for water damage in the electrical components, if these have gotten wet then you run the risk of a fire. Please consider calling an expert in your area to inspect your furnace and make sure the drain line is clear.

Jun 13, 2011 | Intertherm Heating & Cooling

1 Answer

I have an intertherm electric furnace FEH-A020, with multispeed blower installed when A/C added. My problem is blower operation. at the end of the cooling season with fan set to auto operation the fan ran...


The model of T-stat you gave comes up as a discontinued model on Honeywell's web site, but it looks to be a manual stat that type of stat would have to be wired with a summer winter switch with electric heat, allowing it to turn on the fan with a call for heat. If yours is a programmable T-stat you would need to select electric heat or in the installers set up change the default setting for fan from unit controls fan in heat to thermostat controls fan.

Oct 17, 2009 | Intertherm P3RA-048K Air Conditioner

1 Answer

I have a Intertherm heating and air conditioner it is a Manufactured Home. The furnace model number is E2EB-017HA. When you flip the switch to heat and move the control arm up nothing happens. You can go...


When you turn the on/off switch to on you are turning on the "fan switch" and the blower motor is only coming on. When you turn the switch to cool and move the tempature control lever down you are turning on the air conditioner...So it sounds like your heater is not working. Is the heater electronic ignition or does it have a pilot? If it has a pilot the heater may not be working because the pilot is out and will need to be lit. If it is electronic ignition you will need to inspect the unit to determine what component is faulty. Could be the igniter,gas control valve,ect. Verify that gas is not shut off to unit at line valve and gas control valve on unit.

Oct 07, 2009 | Intertherm Heating & Cooling

1 Answer

Intertherm heat coils won't stay off until breakers off,thermostats are off


it is the heat sequencers. it happens all the time. replace them wire by wire to keep it simple. they are located behind the metal next to the breakers they look like this: cdf7518.jpg

Oct 19, 2008 | Intertherm P3RA-024K Air Conditioner

Not finding what you are looking for?
Kitchen Appliances - Others Logo

Related Topics:

261 people viewed this question

Ask a Question

Usually answered in minutes!

Top Kitchen Appliances - Others Experts

Angel Joseph Jr.
Angel Joseph Jr.

Level 2 Expert

683 Answers

kakima

Level 3 Expert

102366 Answers

yadayada
yadayada

Level 3 Expert

70347 Answers

Are you a Kitchen Appliances - Other Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...