I have a APC Silcon 20KVA UPS which got hit by lightening. Now when the power is restored the fuses get burned. We found the PSU board to be defective. Can somebody tell me the dc output voltage from the PSU board.

Posted by on

2 Answers

  • Level 1:

    An expert who has achieved level 1.

  • Contributor
  • 1 Answer

Hi, I have apc silcon 20kva ups my ups is working fine but display scree the ups front door machine language what i m doing.
regard

Posted on Mar 12, 2011

  • Level 1:

    An expert who has achieved level 1.

    Mayor:

    An expert whose answer got voted for 2 times.

    Problem Solver:

    An expert who has answered 5 questions.

  • Contributor
  • 5 Answers

Yes,

You can check PSU out put on Capasitors which install on output.
One of 470mf 25v and other 5 capasitor 1000mf 25v.
on all capasitors 13.3vdc and 5.4vdc will correct volts.

mian_apc@yahoo.com

+92-323-4756564

Regards,

Posted on May 14, 2009

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

UPS SILCON SL30KFB2 ON DISPLAY SAYS "COMMUNICATION TO CONTROLLER LOST", NO COMMAND FROM DISPLAY, ITS IS FROZEN


first check what display and buttons still work?
if there is a problem with the buttons, you have to replace a set of

Oct 04, 2013 | APC Silcon SL30KF (SL30KFB2-TU) UPS System

1 Answer

Silcon DP360, 3-phase 60kva, 400v, year 1993 1. Its old but working perfectly, after I changed the battery bank, because of collapsed cells, it still runs as expected but, I cant get any power readings...


#1. You should call APC Technical Support. It's free, and they will help you. You should get voltage even without a load on the unit.

#2. There is a Tripple-Slot unit for this device. It's specific for the Silcon based units. Read the manual, and there is a PN that you need for it. If it doesn't say SILCON, then it won't work. (I tried).

Paul
Data Centers Canada
www.datacenterscanada.com

Jan 28, 2011 | APC Silcon UPS System

1 Answer

Password Protected for a UPS APC Silcon SL60KF


For Silcon UPS you must ask the person who install the unit if he change the password but for the defualt calibration password is 090909

Aug 07, 2009 | APC Silcon UPS System

1 Answer

Bypass procedure SL20KHB2


First Press the user menu button
then scroll up or down till you reach on put UPS on bypass? Press C to change to YES if the default is already YES just press the # button then the UPS will go on bypass mode.

Go to UPS bypass panel and turn the bypass switch to (1) ON and Switch the Output on the bypass panel to off. Now you're already on a bypass mode.

if you have any query please drop me an email.

Thanks

Feb 20, 2009 | APC Silcon UPS System

2 Answers

APC silcon 40KVA UPS


I understand your problem,

You can chack PSU which instal with controller card.

Your ups will ok after replacment or repairing PSU.

mian_apc@yahoo.com

Regards,

Mar 07, 2008 | APC Silcon UPS System

Not finding what you are looking for?
APC Silcon UPS System Logo

Related Topics:

357 people viewed this question

Ask a Question

Usually answered in minutes!

Top APC UPS Battery Backup Systems Experts

Cindy Wells

Level 3 Expert

4756 Answers

Jax Planet
Jax Planet

Level 2 Expert

921 Answers

Donald DCruz
Donald DCruz

Level 3 Expert

17129 Answers

Are you an APC UPS Battery Backup System Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...