Question about Procom QN300TYLA Compact Heater

Open Question

I need a burner for a Pro-Com LP heater. Where can I buy parts?

Model SSU320RHL-GB (SN: 3715728). 2003 year

Posted by on

2 Suggested Answers

mxc2
  • 146 Answers

SOURCE: heater will ignight and burn for about 5min. then

Cleaning the Pilot/ODS is parts of what should be done but you should also check the thermocouple.

Here is a link to the instructions:

http://www.msservice.net/ts/reseat_thermo-clean_pilot-ODS.htm

This should take care of your problem if this does not take care of the problem then you may need to replace the thermocouple.

Posted on Oct 04, 2010

mxc2
  • 146 Answers

SOURCE: I Need to know whaat type of regulator is need for

Here is a link to the owners manual and page 8 and 9 tell you about the regulator.

http://www.northerntool.com/downloads/manuals/177883.pdf

You need to a 8-11WC regulator for propane and if you are using natural gas you will want to keep the pressure between 3-10WC

If this is connected to a propane bottle you want o use at least a 100lb bottle.

Thanks

Posted on Oct 16, 2010

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

I have a dyna glo RMC 40 NGT vent less wall heater that I would like to convert to propane, I need to know which conversion kit to buy, and where. Thank you.


dyna glo natural gas heater Questions & Answers - Fixya

www.fixya.com > Forum > Tags
dyna glo ventless rmc50 ngt can this heater be changed from natural gas to propaneuse, ... Dyna Glo Natural Gas conversion to LP Gas I have a Dyna-Glo natural gas space ... Question about D-E36 Infra-Red Wall Mounted Panel Heater ... dyna glo heater model #RMC-40GT I believe on your particular model , that you ...

Parts for Dyna Glo, Thermoheat and Dyna Glo Pro Heaters

spaceheaterparts.com/category.sc?categoryId=13
Shop Dyna Glo, Thermoheat, Dura Heat, Workhorse LP and oil fired htrs ... Circuit Board 2201181 Dyna Glo & Thermoheat 150k Nat Gas Htr RMC-FA150NGDGD ... This spark plug (ignitor) is used on Dyna Glo and Thermoheat 40K btu LP.

Propane Wall Heaters - Walmart.com

www.walmart.com > ... > Heaters

WalmartDyna-Glo IR18NMDG-1 18,000 BTU Natural Gas - Infrared Vent Free Wall Heater. $170. ... Dyna-Glo 40K Liquid Propane 360-Degree Tank Top Heater. $88.00 ... Dyna-Glo Deluxe RMC-FA125DGD Portable Gas Powered Forced Air Heater.

1352062 Dyna Glo Natural Gas conversion to LP Gas

162.220.53.34/F/.../t1352062-dyna_glo_natural_gas_conversion_lp_gas

Jan 12, 2016 | Heating & Cooling

1 Answer

Pro Con ssu320rhl-gb. Where can I get a replacement receiver board?


You may have to contact Pro Con directly to determine availability and source.

Dec 22, 2015 | Heating & Cooling

2 Answers

Burner comes on at 3.any lower goes out.6 inch yellow flamestarts on rite side under pressure.not burner rite of burner


Troubleshooting :: AZ Patio Heaters and Replacement Parts

azpatioheaters.com/pages.php?pageid=11
How do I replace starting striker switch on a tall patio heater? How do I clean ... Why is my burner flame low? Why does ... Why does my pilot light, but goes out when heateris turned on high or low? Why do I get a yellow flame and black smoke? ... 6. Can I convert my LP gas patio heater into a natural gas patio heater? NO.

Nov 17, 2015 | Heating & Cooling

1 Answer

I have a Model 200209 LP heater. It worked fine one night. Then, about a month later, it would not light and stay lit and I could only light it with a match. After looking closer, I saw that the pilot...


Clean the pilot using a can of compressed air with a straw nozzle (like you clean your computer with) and while you're at it, clean the burner, using a brush and the canned compressed air to blow it out. Insects like to build nest in these heaters when they're not in use.

Be sure to turn the LP gas tank OFF and disconnect the hose from the tank, before attempting any cleaning. When you reconnect the hose to the tank, open the gas valve VERY, VERY SLOWLY (Slow motion, slow) until it's fully open. Then light the pilot & hold the control knob in for 30 to 60 seconds, before releasing it and turning it to the ON position.

Hope this helped you and thanks for choosing FixYa.

Sep 19, 2011 | Endless Summer 200209 Open Flame Patio...

1 Answer

I have a SSU320RHL-GB the unit works well in the automatic mode with the remote but when you try to go to the manual override the pilot will not stay lit, it lites but will not stay lit. It is very...


That is very odd. I've been in the hearth business for 15 years and have never been faced with this problem. Although, I suspect the remote receiver box is the is the culprit. To test this theory, turn the receiver box OFF. If you're unable to do that, remove the batteries from the receiver box and try operating the stove manually. If it then operates manually, it may be the reciever is wired incorrectly or the 3 position rocker switch on the stove, needs to be switched from Remote to ON. That would then override the remote receiver.

Hope this helps you and thanks for choosing FixYa.

Aug 18, 2011 | Procom SSU320RHN-GB Heater

1 Answer

What do i need to do to switch from LP to NG?


a kit from lp to nat gas orfice for the burner pilot orfice and new reg spring try national energy for thr parts they are on line

Jan 07, 2011 | Procom ML300HGA Heater

1 Answer

We like to convirt LP Water Heater to Natural Gas Water Heater, PG & E told us to replace pilot burner orifice. My question is , 1- is it possiable to do that? 2- If it is What is the part number...


yasharer,

Yes it is possible to convert any gas appliance to natural gas or from natural gas to LP. The only difference is the size of the orifice used in the burner. I have a tip at http://www.fixya.com/support/r7207798-changing_gas_appliance_from_natural_gas which explains everything you will need to know to get the part and change it out.

Thanks for using FixYa and for the great rating.

hardrocko

Dec 10, 2010 | Heating & Cooling

1 Answer

I Need to know whaat type of regulator is need for model ssu320rhl-gb Please


Here is a link to the owners manual and page 8 and 9 tell you about the regulator.

http://www.northerntool.com/downloads/manuals/177883.pdf

You need to a 8-11WC regulator for propane and if you are using natural gas you will want to keep the pressure between 3-10WC

If this is connected to a propane bottle you want o use at least a 100lb bottle.

Thanks

Oct 15, 2010 | Procom SSU320RHN-GB Heater

1 Answer

We have a dynna glo zero clearance for Natural Gas


Before you attempt to covert to lp. You need to check the flue. Black smoke is cause by incomplete combustion. So it may be now plug with black soot. Heat-exchanger may be damage Before you invest in a lp kit. Make sure it is worth it. To convert you need the main burner orifices and lp spring for gas value. Once you replace these parts you must adjust gas pressure, nat gas is measured at 3.2 - 3.5wc lp is measured 10.5 - 11.00 wc. In my honest opinion this is to dangerous for customer to attempt. Please a HVAC contractor inspect unit and install lp kit.

Nov 20, 2009 | Dyna-Glo D-E37 Wall Mounted Panel Heater

Not finding what you are looking for?
Procom QN300TYLA Compact Heater Logo

Related Topics:

76 people viewed this question

Ask a Question

Usually answered in minutes!

Top Procom Heating & Cooling Experts

paulcarew

Level 3 Expert

2046 Answers

Dan Webster
Dan Webster

Level 3 Expert

8205 Answers

john h

Level 3 Expert

7409 Answers

Are you a Procom Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...