Generic problem for all Goodman Air Conditioners

Enduced draft motor runs continuously




By IdahoHVAC on Dec 01, 2008

" "
Enduced draft motor runs continuously with or without call for heat...
Comments:

Dec 02, 2008

- It was the board, and the flame sensor was a second problem, those together made for a confusing diagnosis... Thanks

Best Solution

posted on Dec 01, 2008
Very Helpful)

Accurate Joe

Rank: Guru 
Rating: 87%, 33 votes
Change the board that controls the draft motor. It has froze the contacts. Make sure you check capacitor on motor,and amperage of motor as sometimes this is the cause.
Was this helpful?
Yes
No

Popular Solutions for Air Conditioners


Questions and Unsolved Problems for Air Conditioners


Answer
what french door fridge is good to buy

Answer
I'm looking for good dig cam

Answer
I have a Pinguino classic air conditioner it runs for approc 3 minutes and then the alarm light goes... (More)

Answer
how posibul restore option

Answer
Unit blowing out warm air only (not cooling). Timer light flashing, cannot stop it. Units all... (More)


Didn't find what you were looking for?

Describe your Air Conditioners problem:

Select a Category:







Ask our Experts

 

Solve Your Problem Now!
Chat Live with an Expert
Chat Now
Top Air Conditioner Experts



Top Air Conditioner Repairmen
in Newport, KY
ARS
(866) 800-3823
When it comes to air conditioning systems,...
ARS

Service and Repair, System Maintenance, Advantage...
Aire Serv Heating & Air Conditioning


       
Solve Your Problem Now!
Chat Live with an Expert
Chat Now

Insert Link
Insert Image
Insert You-Tube clip
Insert List
Insert List
Spell Check

What is this?



Select