Question about Combi Centre DX - Mango

1 Answer

Boiler flames extinguish and reignite regularly

I have a 5 year old microgenus 27 Ariston water boiler. Recently the flames have been going on and off in both hot water and central heating modes whilst the fan has continued to run. So from the tap I get hot then cold then hot etc. With the heating on the radiators take ages to warm up because the flames are out more than they are on.
5 visits from Ariston nominated engineers have resulted in renewals of the thermistors, the electrical control panel, the air pressure switch, the main flow control valve and the cleaning out of the heat exchanger,with no success. In fact after the APS was changed the hot water was on for even less time than originally so it was worse still. The APS was part 571651 which the Ariston tech department tell me is the correct part,but I have my doubts.
I am now being quoted 2 grand for a new boiler.
Does anybody have any ideas?
Thank you.

Posted by on

  • mak4 Dec 10, 2008

    Hi mate, I have the same issue. I was also getting a flickering fume light and the boiler sometimes cutting out. The fault was a faulty APS. the Microswitch on the APS has a noisy contact. Swapping this out with a known good fixed the problem. In your case it might we worth checking the condition on the cable/connectors related to the APS. Hope this helps.

×

1 Answer

  • Level 1:

    An expert who has achieved level 1.

    Corporal:

    An expert that hasĀ over 10 points.

    Mayor:

    An expert whose answer gotĀ voted for 2 times.

    Problem Solver:

    An expert who has answered 5 questions.

  • Contributor
  • 16 Answers

What about flame rectification probe (flame proving probe)

Posted on Aug 17, 2009

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
goodluck!

Posted on Jan 02, 2017

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

Sorry Terry - I'm not used to this site! Question was - anyone know what the error message E34 means on an Ariston Boiler MicroGenus 24HE please?


The information I have found states it is a problem with the pressure switch. A faulty pressure switch will prevent ignition from occurring. Here is a Youtube video link showing the issue. Reading the comments below may assist you in isolating your problem. Hope this helps!


Ariston microGENUS 24 HE MFFI Error 34

Oct 21, 2015 | Washing Machines

1 Answer

Ariston microgenus he24 fault is e34 but boiler works when front cover is removed


e34 on a ariston is the fan. Boiler fires up with cover off as its getting the air it needs from atmosphere! fan is not running at full speed

Nov 04, 2011 | Combi Centre DX - Mango

1 Answer

My ariston micro genus type c boiler keeps going hot and cold, the heating also switches on and off, any ideas


when was it last serviced?dirt may be a factor,there are many parts that cause this fault in the microgenus so you need someone familer with the product parts playing up could be1.airswitch2motor3flowgroup4ntc you havent mentioned if it needs re-setting

Jan 10, 2010 | Combi Centre DX - Mango

1 Answer

Ariston Gas Boiler error code E02 what is the problem. No other boiler specification on the type of boiler.


i belive you have a ariston microgenus 2,from memory thats the fault code for low water presure,you need to re-presurise to 1 bar

Nov 27, 2009 | Ariston Technologies AWD 121

1 Answer

Ariston Microgenus 27 boiler - leaking motorised valve


The leak is coming from a seal around the pin that the motor acts upon, the seal does not come as a replaceable part on its own, so the whole flow group as it is called will need to be replaced, approximate price 170 to 200 pounds inc vat, makers part no 998613. plus 2 or 3 hours labour of a corgi registered engineer. If your boiler is more than 6 years old and you have not had to replace the fan or other parts yet, then think about getting a new high efficiency boiler, it could be a better long term solution.

Feb 15, 2009 | Combi Centre DX - Mango

1 Answer

MicroGenus27 No Hot Water


check HW and CH temperature probes check secondary heat exchanger for blockage check water pressure switch

Jan 03, 2009 | Combi Centre DX - Mango

1 Answer

Ariston Microgenus 27mffi combi boiler


im an engineer and recently had exactly the same thing with this ariston boiler, i found out it was the the 'air pressure switch', this is a switch which is part of the ignition, it works in conjuction with the fan. when the boiler fires up the air pressure switch makes, if its faulty it can break the circuit mid flow and cause the burner to shut down therefore giving intermittent hot water and heating, theres a possibility that the aps tubes may be damaged as well so ensure they'e condition is good. hope this helps you

Aug 29, 2008 | Combi Centre DX - Mango

1 Answer

Ariston microgenus 27 pressure on 0


Filling loop is underneath the boiler, easily identified as a chrome coloured braided pipe with a black tap at either end. Open right hand tap first then left hand one . Fill system till presure gauge reads just over 1 bar when system is cold. Then turn both taps off.

Jul 08, 2008 | Combi Centre DX - Mango

1 Answer

I have an Ariston Microgenus 27 Combi Boiler


I hate these boilers!

If the pump is not circulating change it. If the pump is ok you may have a blockage in the diverter valve

Apr 04, 2008 | Combi Centre DX - Mango

Not finding what you are looking for?
Combi Centre DX - Mango Logo

957 people viewed this question

Ask a Question

Usually answered in minutes!

Top Combi Baby Gear Experts

paulcarew

Level 3 Expert

2185 Answers

Les Dickinson
Les Dickinson

Level 3 Expert

18357 Answers

ray gallant

Level 3 Expert

40521 Answers

Are you a Combi Baby Gear Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...