Anonymous Posted on Apr 05, 2012

Mhu 75, only one burner lights

Piped 3/4 pipe all the way to heater in garage & dropped to 1/2" last 2'. Only one burner of the five(sometimes 2) lights and then it times out. Could gas pressure cause it? Have tried playing with valve with no changes. Furnace & water heater work fine.

1 Answer

Paul Carew

Level 3:

An expert who has achieved level 3 by getting 1000 points

Superstar:

An expert that got 20 achievements.

All-Star:

An expert that got 10 achievements.

MVP:

An expert that got 5 achievements.

  • Mr. Heater Master 3,807 Answers
  • Posted on Apr 06, 2012
Paul Carew
Mr. Heater Master
Level 3:

An expert who has achieved level 3 by getting 1000 points

Superstar:

An expert that got 20 achievements.

All-Star:

An expert that got 10 achievements.

MVP:

An expert that got 5 achievements.

Joined: Jul 20, 2008
Answers
3807
Questions
2
Helped
1298666
Points
10523

Did you put a drip pocket on the line to the heater

  • Anonymous Apr 09, 2012

    Yes I did. I just had the gas company check the pressure to the house and it was 7WC. They wouldn' check the furnace pressure though.

×

5 Related Answers

Anonymous

  • 288 Answers
  • Posted on Dec 24, 2007

SOURCE: MHU 75 Model Mr. Heater

The roll out switch is a small disc shaped part about the size of a nickle. There may be more than one. anyway there is a button shaped like a small peg in the center if it, push it in and it should stay in. You may need to re examine the limit switch, because this is what it sounds like. they are rated for a set temperature, so your application may need a higher temp. A simple way to check parts like these is to by-pass them by taking the wires off the part and connecting them together. If this solves the problem, that it. My only concern is that this is a new installation, and maybe its not venting adequately or its burning up all the usable air in the room. That's why most of these parts are on the equipment.

Ad

Anonymous

  • 1902 Answers
  • Posted on Feb 15, 2009

SOURCE: propane convection heater won't maintain full flame

Seems like the valve is not opening up fully or the adjustment is out of adjustment. Try adjusting the flame.

Anonymous

  • 51 Answers
  • Posted on Feb 17, 2009

SOURCE: MHU45LP won't fire

The pressure switch to which you are referring is the switch connected to the suction side of your induced draft fan. This pressure switch will have a hose connected between the switch and the induced draft fan. Please let me know if you need any more assistance.

Anonymous

  • 9 Answers
  • Posted on Mar 22, 2009

SOURCE: Heater Burner ignites but main blower motor will not turn on.

it sound like the blower motor may be seizing up. try spining the blade by hand to see if it feels free or not. the motor could be trying to turn but can then tripping itself out on overload. (most motors have built in safety overloads which will trip during an overcurrant event. aka too many amps.) you may have to replace blower motor

Paul Carew

  • 3807 Answers
  • Posted on Jan 15, 2011

SOURCE: My mhu 75 worked just fine until the regulator on

check the flames sencor is clean and the igniter check connections to the board on both wires , check hoses to pressure switch are not cracked or , you could cut off abit off the end to get better connection on the tubes hope this helps

Ad

Add Your Answer

×

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

0helpful
1answer

Bought a sterling 75 c garage heater burner lights but then 24 v transformer burns out

I didn't find that model but did see a pretty standard wiring schematic for Sterling garage heaters in one installation manual. I'm sure they didn't change much. I did notice they use a 50va transformer, not 40 which is likely what is getting used now. Don't think that would fix it, just an idea. Put a 5 amp fuse inline on the red side of the secondary side of the transformer. This will protect it. I'm willing to bet the ignitor section on the low voltage common is wired wrong. Remove the tstat wires, buy a resettable fuse and install it first. Then get the fan running first. If there is a g terminal jump red to green. This is fan only, start simple, hope this helps

If you need further help, reach me via phone at https://www.6ya.com/expert/thomas_092728000e6acb79

0helpful
1answer

Gas heater lights pilot but doesnt light main burner.I turn off the electric quickly and turn it right back on.the pilot lights and main burner will come on. I have to do this every time to get it to...

Before calling service technician, read manual troubleshoot section.
It is possible there is simple do-it-yourself solution.
You posted under Universal Heavy duty 75 gallon commercial water heater.
Open following links to identify specific water heater and download manual:
The manual has wealth of maintenance information that should be done yearly by trained technician, which will genuinely help this $4000 water heater last many years longer than expected.
http://www.rheem.com/products/commercial/water_heating/commercial_gas/
http://www.rheem.com/product.aspx?id=0697944D-D79A-40C1-BDEB-875E48200DD1
http://globalimageserver.com/fetchDocument.aspx?id=c0b73553-5f03-4a5e-8789-4732ffecdccf
http://www.drillspot.com/products/155234/Rheem_G75-125_Commercial_Water_Heater?s=1
0helpful
1answer

I have a RMTG-53dvn piped in parrallel with a traditional water heater because I used to have two traditional in parallel. The unit never kicked on with no trouble code, so I piped in series with a...

I could see how it might not work in parallel. Much water would go thru the conventional heater, so there would be low flow thru the tankless.
Now, the tankless is getting hot water from the conventional. Try shutting the conventional heater's power source off so the water gets cold, then see what happens with the tankless.
Gary
0helpful
1answer

Need a blanket for Rheem Water Heater model #22VRP75.

You have 75 gallon gas water heater.
I install water heater insulation 3 ways:
1) Easiest: buy ready-made blanket from Lowes and use duct tape
2) Harder: wrap heater in ordinary fiberglass insulation and use tie wire
3) Hardest: Build a box out of blue styrafoam >> leaving room for air intake for gas water heater, and space around vent pipe

Instructions for gas water heater:
Do not cover TP valve.
No insulation is put over gas valve or air intake.
No insulation touches vent pipe.
Remember the gas water heater has to breathe air into the burner, and aftter combustion takes blace, hot gases escape so extra space is left around hot vent pipe to avoid fire.

Find age of Rheem: look at 3rd and 4th digit of serial number, for example 06 was manufactured in 2006.

Add a comment for more free help.
Also take advantage of fixya phone service.
For a price, expert speaks with you over phone while you work on water heater or any do-it-yourself project.
Fixya is always less expensive than a service call.
0helpful
1answer

Took apart electrode assembly & cleaned--replaced with proper nozzle .75 x 80A- -re-gapped with beckett gauge---was that rite or is there a gauge for the bock water heater or wayne burner? Nees proper...

The nozzle size and gap completely are designed to each burner, if the bock water heater had a becket burner than you would be okay with the gap, if not then what I would do is check the manufactures manual for proper nozzles and gaps of electrode assembly
0helpful
1answer

My larrs pool heater will ignite,but not stay lit

If your Laars will not stay lit then the pilot generator is faulty. That is the small brass and copper piped connection near the pilot flame. It must produce 250minivolts in order to open the main gas valve and keep the gas running into the pilot burner..

please visit http://www.laarsman.co.uk for more help

Miles X
0helpful
1answer

High Pitched droning noise just after ignition on and andrews R300 boiler. how do you cure? Is it gas pressure related?

If the gas flex line to the unit is to small it will whistle and make a very strange noise while the main burners are on. The gas flex is what connects the unot to the hard piped gas line, replace the gas flex and that will fix it. Note: not a longer gas flex, there should be a tag on it, lets say it's a 1/2", then install a 5/8", ect.
Good Luck.
Paul
0helpful
1answer

Shuts off when switched to low and smells when running.

clean the burner and the orifice you can use a air line or blow off a vacum cleaner
Not finding what you are looking for?

200 views

Ask a Question

Usually answered in minutes!

Top Mr. Heater Heating & Cooling Experts

Paul Carew

Level 3 Expert

3807 Answers

Brad Brown

Level 3 Expert

19187 Answers

Jay Finke
Jay Finke

Level 3 Expert

1397 Answers

Are you a Mr. Heater Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...