Question about Dayton Electric Heater

1 Answer

Dayton electric garage heater

I have a dayton 3UG73D garage heater and everything is properly wired but it only runs on low speed.I can not get it to run on high.

Posted by on

1 Answer

  • Level 1:

    An expert who has achieved level 1.

    Corporal:

    An expert that has over 10 points.

    Mayor:

    An expert whose answer got voted for 2 times.

    Problem Solver:

    An expert who has answered 5 questions.

  • Contributor
  • 8 Answers

Need to check you fan wires, some have differant colors on the moter for the differant speeds, you may need to change the fan speed by unplugging one of the wires and replacing it with another. hopefully you still have the manuel , check with it first!!!

Posted on Jan 07, 2009

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
goodluck!

Posted on Jan 02, 2017

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

90000 btu high intensity infrared ceiling hung heat. Have replace twice and Honeywell gas valve once. Always starts and runs first time then never starts again. Coils on gas valve keep burning up. ??


Dayton 3E134E Troubleshooting guide - manualzz.com

manualzz.com/doc/1285710/dayton-3e134e-troubleshooting-guide
This heater must be installed and serviced by trained gas installation and service ... Dayton High-Intensity Heaters ® Description Dayton high-intensity heaters ... ofinfrared radiation by heating a ceramic refractory material to incandescence. ..... 3E133, 3E461, 5VD63, 5VD64 90,000 BTU/H Do not mount heater horizontally.

[PDF]Fall Heating - Plumbing & HVAC

plumbingandhvac.ca/images/documents/PHVAC_Sept-Oct03.pdf
Nova Scotia gas utility eyes dealer network ... valve underbody and screw trim pieces ... Infrared requires a different way of ... gives you a crisp picture, and speeds up pipe locating. ... tiative will keep HVAC contractors busy ..... labelling for equipment usinghigh pressure R410A ..... Multi fired from 90,000 to 179,000 btu/h.

Jan 05, 2016 | Dryers

1 Answer

How do you change speeds on a dayton 3lu87j motor?


did you install the proper motor run capacitor . any time you change a motor you must replace the capacitor

Nov 24, 2012 | Heating & Cooling

1 Answer

I have a hanging Dayton in garage pilot lights fine furnace fires up runs 6or7 min. then burner and pilot go out


Does unit fan come on ??? Is flue clear as most units have a safety klixon if exhaust not venting properly.

Nov 24, 2012 | Dayton Gas Furnace Heater

1 Answer

I just instlled a Dayton 3UG73D garage heater and the motor has stopped. It still heats up but the motor will not come on


Check for loose or disconnected wire especially to the hi-limit switch or fan switch.

Dec 16, 2009 | Heating & Cooling

1 Answer

My dayton NG heater fan will not shut off properly


Sounds like a bad fan switch. The switch is located on the heat exchanger and is 110 volt bi-metal switch. Follow the wires from the blower going back to the heatexchanger. Graingers can get you a new switch if you give them your model number. www.grainger.com.

Dec 12, 2009 | Dayton Heating & Cooling

1 Answer

I have a 3ug73d heater I would like to put a real thermastat on it.How do i wire it.


is this a baseboard unit? the thermostat kit has four wires - a black and a red, a black and a red. for 240 volt operation, both line wires go on the two blacks and the heater load goes on the red wires

Oct 13, 2009 | Dayton Heating & Cooling

3 Answers

240v circuit wiring to run my new Dayton Heater (3Vu34A)


On the 40 amp breaker, you should be using 8-3 w/ground. 10-3 w/ground will work on the 30 amp breaker. 12-3 w/ground is used for 20 amp circuits. Your new heater should have the electrical requirements listed in the user/installation information.



Jan 29, 2009 | Dayton 3VU34 Heater

1 Answer

Installing a Dayton G73


How many amps is your service? And what gauge wire did you use for the heater?
If your service is only 40amps that is your problem. You don't have enough amps for the heater and the rest of your house, you will have to upgrade your service.

Nov 02, 2008 | Dayton G73 Utility Heater

Not finding what you are looking for?
Dayton Electric Heater Logo

Related Topics:

294 people viewed this question

Ask a Question

Usually answered in minutes!

Top Dayton Heating & Cooling Experts

paulcarew

Level 3 Expert

2304 Answers

Mack Baxter

Level 3 Expert

381 Answers

Dan Webster
Dan Webster

Level 3 Expert

8205 Answers

Are you a Dayton Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...