Try to reset the unit by disconnecting the power supply for 10sec. and operate the unit. If it wont work replace your Room Air and Coil Thersmistor or test the thersmistor with mulitester. The resistance reading of thermistor is 10 kilo ohms @25deg. C room temp. If it is shorted or open the unit wont operate.
×