Question about Air Conditioners

1 Answer

I have a multifuel stove which runs my central heating system from its back boiler. When it gets really hot there is a loud clicking and knocking sound from the rear of the stove where the thermostatic control is. The noise stops when I turn the electric pump off. How do I fix this please?

Posted by on

1 Answer

  • Level 1:

    An expert who has achieved level 1.

    Corporal:

    An expert that hasĀ over 10 points.

    Mayor:

    An expert whose answer gotĀ voted for 2 times.

    Problem Solver:

    An expert who has answered 5 questions.

  • Contributor
  • 15 Answers

That clicking and knocking noise you hear is called cavitation. It's when the bubbles of steam are cooled down rapidly and implode upon themselves. Cavitation is not a good thing to have in a boiler as it can cause dramas. This cavitation is more than likely because the boiler is firing too hot. A service technician should be called to turn the regulator down a little bit.

Posted on Sep 18, 2008

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

2 Answers

The boiler wont fire up and the blue light flashes once per second


Let's see what we can do to trouble-shoot this boiler--

First of all-- Are we talking about a Hot Water 'Boiler'-- In other words does this boiler heat water that circulates thru the house, to keep you warm?

Next-- What is your fuel?

Have you Shut the system down, to reset it?-- What happens when it comes back on again?-- Clicking sounds-- pumps trying to start-- solenoids trying to open, etc.-- Tell us what you observe-- so we can help you trouble shoot this problem.

Mack B

Jan 15, 2011 | Air Conditioners

6 Answers

Boiler doesn't fire up. 25 years old Amana outdoor boiler model #3612M-A Mfg # P68191-1F,It had leak in pump housing and replaced, replaced igniter ,but no fire, no leak in system ,pump are keep running...





How a Central Air Conditioning System Works
amn_howac.jpg


Facts:
  • The typical central air conditioning system is a split system, with an outdoor air conditioning, or "compressor bearing unit" and an indoor coil, which is usually installed on top of the furnace in the home.
  • Using electricity as its power source, the compressor pumps refrigerant through the system to gather heat and moisture from indoors and remove it from the home.
  • Heat and moisture are removed from the home when warm air from inside the home is blown over the cooled indoor coil. The heat in the air transfers to the coil, thereby "cooling" the air.
  • The heat that has transferred to the coil is then "pumped" to the exterior of the home, while the cooled air is pumped back inside, helping to maintain a comfortable indoor temperature.
  • Central air conditioning can also be provided through a package unit or a heat pump.

Benefits:
  • Indoor comfort during warm weather - Central air conditioning helps keep your home cool and reduces humidity levels.
  • Cleaner air - As your central air conditioning system draws air out of various rooms in the house through return air ducts, the air is pulled through an air filter, which removes airborne particles such as dust and lint. Sophisticated filters may remove microscopic pollutants, as well. The filtered air is then routed to air supply ductwork that carries it back to rooms.
  • Quieter operation - Because the compressor bearing unit is located outside the home, the indoor noise level from its operation is much lower than that of a free-standing air conditioning unit.





















ed.

Sep 10, 2008 | Amana Air Conditioners

1 Answer

Central heating system boiling


more information required but if the boiler supplies the domestic hot water cylinder then the stat on the cylinder may be bringing on the boiler also the boiler stat may be up too high try turning it down.

Jan 05, 2009 | Air Conditioners

1 Answer

Bosch greenstar 30 CDi - no central heating or hot water!


it sounds like the system was not cleaned properly when the new boiler was fitted. all new boilers need to have the pipework flushed to remove any debris scale sludge and flux from the system. this is now usually done by a power flush which is basically a big pump mounted on a big bucket and it washes the dirt out of the pipework and collects in the bucket. if this is not done the dirt will block up the small passages in the heat exchanger. i suggest the system is cleaned flush and the heat exchanger changed to help protect the boiler a filter should be fitted (for example a magna clean) if the company who installed the boiler is corgi registered then they are liable for the damages. call corgi for advice.

Jan 04, 2009 | Air Conditioners

1 Answer

Boiler bangs when hot water used


You need to install a "water hammer arrestor" they can be found at any local plumbing supply house.

If you can find one with "Shark bite" fittings already installed then there will be no need for soldering or special tools other than a tubing cutter.

Dec 27, 2008 | Mitsubishi Mr. Slim MXZ30TN Air...

1 Answer

Ariston micro genus combi boiler central heating works okay but domestic hotwater fails to rise but burners seem to be lit and the boiler doesnt appear to cycle dhw temp gets to about 30 degrees instead of...


having found a circuit diagram, realised that the divertor valve was electrically operated.i unplugged this then unclipped the motor from the valve body,the diverter valve is spring loaded and once i'd removed the motor the spring raised the valve to divert water through the dhw heat exchanger,giving us hot water but no heating, if i refit the motor the problem comes back heating no dhw.ordered new motorised valve assembly £30 next day order .
this was a simple fix without having to drain the system down.

Dec 07, 2008 | Air Conditioners

1 Answer

Have an oil fired boiler for baseboard heat and it also has a tankless heater for domestic hot water. No heat being called for only getting hot water for use. Boiler goes to 210 degrees before it knocks...


These boilers usually have multiple controls. The control that would take it out of the circuit at 210 degrees is a safety.

You should definitely have a professional take a look at this unit before you continue using it.

Sep 18, 2008 | Air Conditioners

1 Answer

My central heating system comprises a worcester bosch system boiler and honeywell smartfit controls. The problem I am having is that the central heating doesn't seem to knock off at the preset temperature...


You could possibly have an ignition problem. The controller will go into a lock-out condition if flame is not established. Turning the temperature control down and then back up may be serving to reset the control system so it tries again.

May 21, 2008 | Honeywell Air Conditioners

Not finding what you are looking for?
Air Conditioners Logo

Related Topics:

155 people viewed this question

Ask a Question

Usually answered in minutes!

Top Air Conditioners Experts

Dan Webster
Dan Webster

Level 3 Expert

8147 Answers

Bill Long

Level 3 Expert

577 Answers

Tim Whalen

Level 3 Expert

3056 Answers

Are you an Air Conditioner Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...