run from the other terminal of the new capacitor to the "COM" on the old capacior. What you are doing is bypassing the fan side of the old capacitor but still using the compressor side of the old Cap.
bypass the circuit containing the low and high pressure cutoff switches. I'm guessing the capacitor problem shut down the fan, leading to an overpressure on the compressor - tripping (or damaging)
capacitor, black to contact, and purple to df1 on the defrost timer board). The contactor appears good it plunges when I give it power and the compressor comes on. Wondering if the defrost timer board
capacitor and check for a short if you suspect it; but it would be warm someplace. The timer unit is usually reliable, but if it permits a thermal cutout after 5 min. and the cutout device is a little
Question about Heating & Cooling
...bypass) the therm and unit does not shut off then you have found the culprit. the outside fan has to run to cool the condenser unit that electrical motor is controlled by start/run capacitors ,in the ...
...that the insulation on one of the start or run windings has overheated and broken down. Before you give up though, you can try to change the compressor capacitor, with same rated microfarad
Question about Goodman Manufacturing Heating & Cooling
run\start capacitor and the hard start cap. I still have the same problem. I don't know if I have a bad circuit board or the wrong one. It seems the run circuit is the problem but I don't know. I also
...capacitor. In american air conditioners the cap has 3 sections all clear marked. The fan has an F and only 2 terminals, the compressor has a HERM (for hermedically sealed compressor) and only 3 ...
...bypass the cooling on the stat I assume nothing is running. FIRST: make sure you don't have a blocked drain and a float switch keeping it off!!! Float could be in pvc line (has 2 wires to it) . if ...