Kenmore 6000 BTU Single Room Air Conditioner "conditioner fan hitting water" Questions

Ad

Question about Frigidaire Heating & Cooling

2 Answers

Conditioner and it was working fine. But there was noise from back of the ac, something hit by fan. So I figured there was something loose so I opened again found out that there is water sitting there

Ad

Question about LG Heating & Cooling

1 Answer

...fan is hitting water as it blows. AC units do take the humidity out of the air and water collects in the bottom. The unit should be tilted slightly downward on the outside so that the water runs ...

Ad

Question about Haier Heating & Cooling

1 Answer

fan blades hitting condensation water. If your unit is installed properly (very slight tilt down in back) no water should come back into the living area. Water is suppose to be splashed up against the

Question about Amana Heating & Cooling

1 Answer

...fan. also sprittsing water coming in house. Hi, The drain hole is plugged by dirt and/or dust.... Here is a tip about trouble shooting your air conditioner... Air Conditioner Trouble -Review the ...

Question about Maytag Heating & Cooling

2 Answers

fan hitting. 7 years old should I replace with new one? It does have a fan and something could have become misaligned allowing the fan to hit the evaporator or it could be icing up and the fan hitting

Question about Kenmore Heating & Cooling

1 Answer

...Conditioner #253.70062. I installed in my window yesterday and there is water running from the top of the unit down and when it hits the fan it is spitting the water out. Is there not a place for the ...

...fan is hitting water, also throwing off a water mist. Water not draining from air Conditioner Look outside the unit, unless you are very high in the air and clean out the condensate\water drain hole. ...

Question about Haier Heating & Cooling

2 Answers

...fan blades hitting backed up water in the drip pan. This occurs when the drain hole near the rear of the drain pan is clogged and/or the rear of the unit does not have enough downward tilt. Which ...

Question about Haier Heating & Cooling

1 Answer

...Where the unit drains is clogged it sounds like so your fan blade is hitting the water and scooping some of that water indoor. look where the condensate drains and clean that and it should be ...

Question about Rheem Heating & Cooling

1 Answer

...hitting outside fan Dripping water freezing to hit outside fan It sounds like your system might be low on coolant. Check the pressure of the main line and check it against the specs. You may have a ...

Not finding what you are looking for?
Heating & Cooling Logo

13 questions posted

Ask a Question

Usually answered in minutes!

Top Kenmore Heating & Cooling Experts

Jay Finke
Jay Finke

Level 3 Expert

1397 Answers

ZJ Limited
ZJ Limited

Level 3 Expert

17989 Answers

Brad Brown

Level 3 Expert

19187 Answers

Are you a Kenmore Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...