I replaced the pilot generator and pressure valve (it was leaking) but can NOT get the burner to light. I bypassed all safty's and the burner still will not light. I read in another thread to jump the "TH" connections on the gas valve. I will try that.
I don't know if the gas valve or the temp controll unit is bad.
Other suggestions from anyone?? All help is appreciated.
Thanks, Goober444
Have you checked your pilot generator voltage while everything is connected properly? You may have a shorted wire or limit or even thermostat. If you jump the TH connections on the gas valve, it would lead to shorted, inoperable safety, thermostat.
If everything is connected properly, the MV reading should be 500+, less than this and you are losing power somewhere.
Have you checked your pilot generator voltage while everything is connected properly? You may have a shorted wire or limit or even thermostat. If you jump the TH connections on the gas valve, it would lead to shorted, inoperable safety, thermostat.
If everything is connected properly, the MV reading should be 500+, less than this and you are losing power somewhere.
×